General Features |
- External transmitters or signal conditioners can be eliminated by direct connection of the sensor output to more than
38 Plug-in Input Signal Conditioners that include:
AC/DC Current Pressure Resistance
AC/DC Voltage Process *Temperature
Load Cell Prototype 4 to 20 mA
*See model BL-40H and DL-40H for higher accuracy digitally linearized thermocouple and RTD
- Optional isolated 16 bit analog output. User or factory scalable to 4 to 20 mA, 0 to 20 mA or 0 to 10 V across any desired digital span from ± one count to the full scale range of 1999 to 9999 (12000 counts).
- Auto-sensing AC/DC power supply. For voltages between
85-265 V AC / 95-370 V DC (PS1) or 18-48 V AC / 10-72 V DC (PS2).
- 24 V DC excitation is available to power external transmitters and 5 or 10 V DC excitation is available for resistance bridge type sensors such as Load Cells and Pressure Transducers.
- Standard red or optional green or super bright red 4-digit LED with display range 1999 to 9999 (12000 counts).
- Red or green 0.8 LED large display option
- Three annunciator LEDs provide front panel alarm status indication for up to four setpoints.
- Two 10 Amp Form C and two 5 Amp Form A relay, or optionally four 5 Amp Form A are available.
- Automatic intelligent averaging smoothes noisy signals, while providing a fast display response to real level changes.
Software Features |
Three-button front panel programming of;
- Decimal point setting.
- Four-level brightness control of digital display.
- Peak and valley view and reset.
- Four programmable setpoints.
- Adjustable delay-on-make and delay-on-break time for setpoints 1 and 2.
- Relay activation can be selected to occur above (HI) or below (LO) each setpoint.
- Hysteresis setting for all four setpoints (if four relays are installed).
Input Module Compatibility |
LEOPARD FAMILY: Accepts more than 38 different Plug-in I-Series Input Signal Conditioners approved for Texmates Leopard Family of meters.
Specifications |
- Input Specs: ...... Depends on Input signal conditioner
- A/D Converter: ...... 14 bit single slope
- Accuracy: ...... ±(0.05% of reading + 2 counts)
- Temp. Coeff.: ...... 100 ppm/°C (Typical)
- Warm up time: ...... 2 minutes
- Conversion Rate: ...... 5 conversions per second (Typical)
- Display: ...... 4 digit 0.56" Red LED display (std), 0.56 or 0.8" Red, Green or Super Bright Red (optn) Range 1999 to 9999 counts.
- Polarity: ...... Assumed positive. Displays negative
- Decimal Selection: ...... Front panel button selectable, XXXX
- Positive Overrange: ...... Top segments of digital display flash
- Negative Overrange: ...... Bottom segment of digital display flash
- Relay Output: ...... Two 5 A Form A relays and two 10 A Form C, or 5 A form A relays.
- Analog Output: ...... Isolated 16 bit user scalable mA or V
AIC (mA out) 4-20 mA @ 0 to 500 ohms max loop resistance
AIV (volts out) 0-10 V DC @ 500 ohms or higher resistance
- Power Supply: ...... AC/DC Auto sensing wide range supply
PS1 (std) 85-265 VAC / 95-370 VDC @ 2.5W max 3.5W
PS2 18-48 VAC / 10-72 VDC @ 2.5W max 3.5W
- Operating Temp.: ...... 0 to 60 °C
- Storage Temp: ...... 20 °C to 70 °C.
- Relative Humidity: ...... 95% (non condensing)
- Case Dimensions: ...... 1/8 DIN (Bezel 96Wx48Hmm)
Depth behind bezel (4.61) 117 mm
Plus (0.57) 14.5mm for connectors
- Weight: ...... 6.5 oz., 8.5 oz when packed
|